ADDITIONAL SCALING PARAMETERS
B2800 Simplified 4-20mA Programming Instructions
Note: If your B2800 Flow Monitor was ordered with a Blancett Turbine Flow Meter, the 4-20mA was programmed and factory calibrated.
Flow 4 mA Setting – When the loop powered option is ordered, the flow rate that corresponds to 4mA must be
set. Zero is default flow rate for this setting. If the current selection is correct, press the ENTER key once to
advance to the next parameter. If adjustment is required use the
arrow key to select the position of the
number you wish to change, then, use the
arrow key to increment the number. Once you have completed this
step, press the ENTER key to advance to the next parameter.
Flow 20 mA Setting – The flow rate that corresponds to 20mA must set next. The turbine meter’s maximum
flow rate is the default value. If the current selection is correct, press the ENTER key once to advance to the
next parameter. If adjustment is required use the
arrow key to select the position of the number you wish to
change, then, use the
arrow key to increment the number. Once you have completed this step, press the
ENTER key to advance to the next parameter.
4-20 mA Calibration – When ordered with a 4-20 mA option this menu item allows the fine adjustment of the
4-20 mA output. The 4 mA setting is typically between 35 and 50. To set the 4 mA value, connect an ammeter
in series with the loop power supply. At the 4 mA OUT prompt, adjust the 4mA value to obtain a 4mA reading
on the ammeter. The
arrow key increments the value and the
arrow key decrements the value. When a
steady 4mA reading is obtained on the ammeter, press the ENTER key to lock in this value and move to the
20mA adjustment. The 20mA adjustment is performed using the same procedure as the 4mA adjustment.
4-20 mA Test – The monitor contains a diagnostic routine that allows the simulation of mA values between 4
and 20 to check output tracking. At the 4-20TEST prompt the arrow keys change the simulated mA output in
increments of 1mA. The ammeter should track the simulated mA output. If a 4-20mA test in not necessary,
pressing the ENTER key once will escape the testing at any time.