Series 3050Data Industrial® Series 3050 Btu MonitorInstallation & Operation Manual941700-0030 (6-11)IMPORTANT: This manual contains important inf
Page 10 6-11Series 3050 Btu MonitorAnalog InputAs an alternative to the pulse inputs, the Series 3050 can accept an Analog input. The input is
Page 116-11Installation & Operation ManualTemperature InputThe Series 3050 Btu Monitor can accept inputs from either a pair of thermistors or RTDs
Page 12 6-11Series 3050 Btu MonitorSolid State Switch and Form “C” Output Wiring The Series 3050 Btu Monitor has one Normally Open (N.O.) soli
Page 136-11Installation & Operation ManualFigure 8 Relay and Switch Wiring Examples (continued) ( Chiller Control based on High Energy Usage with
Page 14 6-11Series 3050 Btu MonitorOUTPUT OPTION CARDIf the Series 3050 Btu Monitor was ordered with the Output Option card, it will have seve
Page 156-11Installation & Operation ManualModbus pointsAll of the following are available as Input Registers.Addr Function1. Flow 1 Rate (GPM)
Page 16 6-11Series 3050 Btu MonitorDISPLAY AND KEY PADThe Series 3050 Btu Monitor has a two line by 16-character display with two modes of ope
Page 176-11Installation & Operation ManualPROGRAMMINGWith the normal mode display showing, pressing the Menu key will enter the programming mode.
Page 18 6-11Series 3050 Btu MonitorPage 13 Programming Flow Chart
Page 196-11Installation & Operation Manual
Series 3050 Btu MonitorPage ii 6-11
Page 20 6-11Series 3050 Btu MonitorPage 15
Page 216-11Installation & Operation ManualPage 16
Page 22 6-11Series 3050 Btu MonitorPage 17
Page 236-11Installation & Operation ManualPage 18
Page 24 6-11Series 3050 Btu MonitorUSB CommunicationIf the Data Industrial Series 3050 Btu Monitor is ordered with an Analog Output Option car
Page 256-11Installation & Operation Manual4. Run HyperTerminal (from the Windows Start Menu) and create a new connection with a name and icon. 5.
Page 26 6-11Series 3050 Btu MonitorUSB COMMAND LISTIn the list below, brackets indicate an argument, specifying its type and value range. For
Page 276-11Installation & Operation ManualBTU CONFIGURATIONBtu rate units = [0-5] – set the Btu rate units: 0: kBtu/hr 1: Btu/min 2: kW 3: TR
Page 28 6-11Series 3050 Btu MonitorRS485 COMM PORT CONFIGURATIONcomm baudrate = [0-7] 0: Auto 1: 300 2: 1200 3: 2400 4: 9600 5: 19200 6
Page 296-11Installation & Operation ManualFLOW SENSOR INPUTSType Threshold Signal Limit Frequency Pull-up Impedance Aux. Power CalibrationPulse-Di
CONTENTSINTRODUCTION ...
Page 30 6-11Series 3050 Btu MonitorIntentionally blank page
Page 316-11Installation & Operation ManualIntentionally blank page
Please see our website at www.badgermeter.comfor specic contacts.Data Industrial is a registered trademark of Badger Meter, Inc.Other trademarks appe
Series 3050 Btu MonitorPage iv 6-11
Page 56-11Installation & Operation ManualINTRODUCTIONThis manual provides installation and operation instructions for the Badger Meter Data Indust
Page 6 6-11Series 3050 Btu MonitorSeries 3050 Btu Monitor Programming The user can program the flow sensor from the front panel by entering a
Page 76-11Installation & Operation ManualINSTALLATIONMechanical InstallationThe Series 3050 Btu Monitor can be either panel mounted or wall mounte
Page 8 6-11Series 3050 Btu MonitorWall Mount Installation The Series 3050 wall mount is designed to mount onto a wall with four bolts or screw
Page 96-11Installation & Operation ManualFlow Sensor Wiring The Series 3050 flow sensor inputs are extremely versatile, designed to accept either